All Products FAQs Contact Us
Location: Home Page >> Moulded Case Circuit Breakers >> SD, CS Series Moulded Case Circuit Breaker

SD, CS Series Moulded Case Circuit Breaker


SD, CS Series Moulded Case Circuit Breaker - Moulded Case Circuit Breakers - Circuit Breaker
 

Overvies of SD/CS family:

MCCBs for power distribution     SD100 SD160 CS100
Frame size   [AF] 100 160 100
Rated current,In@   [A] 16,20,25,32,40,50,63,80,100 100,125,160 40,50,63,80,100
No. of poles     2*,3,4 2*,3,4 2*,3,4
Rated operational voltage,Ue AC [V] 690 690 690
DC [V] 500 500 500
Rated impulse withstand voltage,Uimp   [kV] 8 8 8
Rated insulation voltage,Ui     750 750 750
Rated ultimate short-circuit breaking capacity,Icu   [V] N H L N H L N H L
AC 50/60Hz 220/240V [kA] 85 100 200 85 100 200 100 120 200
380/415V [kA] 50 85 150 50 85 150 50 85 150
440/460V [kA] 50 70 130 50 70 130 50 70 130
480/500V [kA] 30 50 65 30 50 65 42 65 85
660/690V [kA] 5 8 10 5 8 10 10 15 20
DC 250V [kA] 42 65 100 42 65 100 50 85 100
DC(2poles in series) 500V [kA] 42 65 100 42 65 100 50 85 100
Rated service breaking capacity,Ics   [%Icu] 100% 100% 100% 100% 100% 100% 100% 100% 100%
MCCBs for motor protection          
Frame size   [AF] - - 100
Poles     - - 3
Operational voltage,Ue   [V] - - 690
Breaking capacities     - - N H L
Icu at 380/450V [kA] - - 50 85 150
Trip unit Magnetic only   - -
Switch-disconnectors          
Rated thermal current,Ith   [A] - 160  
Rated operatinal current,Ie   [A] - 160  
Poles     - 2,3,4  
Operational voltage,Ue AC 50-60Hz [V] - 690  
DC [V] - 500  
Rated short-circuit making capacity,Icm   [kA peak] - 3.1  
Rated short-time withstand current,lcw 1s [A rms] - 2200  
3s [A rms] - 2200  
20s [A rms] - 96  
Basic dimensions     W H D W H D W H D
Front connection 3-pole [mm]

90

140 86

90

140 86 105 160 86
4-pole [mm] 120 140 86 120 140 86 140 160 86

CS160 CS250 CS400 CS630 CS800
160 250 400 630 800
100,125,160 125,160,200,250 300,400 500,630 700**,800
2*,3,4 2*,3,4 2*,3,4 2*,3,4 2*,3,4
690 690 690 690 690
500 500 500 500 500
8 8 8 8 8
750 750 750 750 750
N H L N H L N H L N H L N H L
100 120 200 100 120 200 100 120 200 100 120 200 100 120 200
50 85 150 50 85 150 65 85 150 65 85 150 65 100 150
50 70 130 50 70 130 65 85 130 65 85 130 65 100 130
42 65 85 42 65 85 42 65 85 42 65 85 42 85 100
10 15 20 10 15 20 10 20 35 10 20 35 10 20 35
50 85 100 50 85 100 50 85 100 50 85 100 50 85 100
50 85 100 50 85 100 50 85 100 50 85 100 50 85 100
100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
         
160 250 400 630 800
3 3 3 3 3
690 690 690 690 690
N H L N H L N H L N H L N H L
50 85 150 50 85 150 65 85 150 65 85 150 50 100 150
         
160 250 400 630 800
160 250 400 630 800
2,3,4 2,3,4 2,3,4 2,3,4 2,3,4
690 690 690 690 690
500 500 500 500 500
3.6 4.9 7.1 8.5 12
2500 3500 5000 6300 8000
2500 3500 5000 6300 8000
960 1350 1930 2320 2560
W H D W H D W H D W H D W H D
105 160 86 105 160 86 140 260 110 140 260 110 210 320 135
140 160 86 140 160 86 85 260 110 85 260 110 210 320 135

*2 pole MCCB in pole frame size **700A only available for SD800FTU @Applicable to MCCBs equipped with FTU, FMU, ATU

MCCBs for Power Distribution
Type ABE 52 ABE 63 ABE 104 ABE 203 ABE 403
Rated Current In(A) 40℃
Reference ambient temperature 40℃
10, 15, 20, 30, 40, 50 60 15, 20, 30, 40, 50, 60, 75, 100 125, 150, 175, 200, 225 250, 300, 350, 400
Number of Poles 2 3 4 2 3 4 2 3 4 3 3
Max Rated Service Voltage Ui(V) AC 600 600 600 600 600
DC 250 250 250 250 250
Dimensions and Mounting Details   a 50 75 100 50 75 100 2 3 4 105 140
b 130 130 130 165 257
c 56 56 56 56 95
ca 82 82 82 84 145
bb 110 110 110 125 215
aa 0 25 50 0 25 50 0 25 50 35 44
Dimensions and Mounting Details(KA) GB14048-2
AC(No symmetry value/symmetry value)
550V 600V 2.5 2.5 5 7.5 0
440V 480V 2.5 2.5 7.5 10 25
380V 7.5 7.5 14 18 30
220V 240V 10 10 25 35 35
IEC60947-2
Icu
AC
500V 2.5 2.5 5 7.5 18
440V 5 2.5 7.5 10 25
415V 5 5 10 10 25
380V 7.5 5 14 18 30
240V 10 10 25 35 35
DC 250V 2.5 2.5 5 10 10
125V - - 10 15 20
Connection Way Press termianl
Shopping Fitting Alarming Switch(AL) - o - -  
Auxiliary Switch(AUX) - o - - o
Voltage Release Mounting(SHT) - o - - o
Low Voltage Release Mounting(UVT) - o - - o
Accessory Lead Wire Terminal Platform(LT) - o - - o
Outer Operate Handle - o - - o o
Terminal Isolation Cover o o o o o
Automatic Tripping Device Complete electromagenetism type Thermal electromagenetism type - - Thermal electromagnetism type
Trip Button - Have - Have

Type ABS 32 ABS 53 ABS 64
Rated Current In(A) 40℃
Reference ambient temperature 40℃
3, 5, 10, 15, 20, 30 10, 15, 20, 30, 40, 50 60
Number of Poles 2 3 4 2 3 4 2 3 4
Max Rated Service Voltage Ui(V) AC 600 600 600
DC 250 250 250
Dimensions and Mounting Details   a 50 75 100 50 75 100 2 3 4
b 130 130 130
c 56 56 56
ca 82 82 82
bb 110 110 110
aa 0 25 50 0 25 50 0 25 50
Dimensions and Mounting Details(KA) GB14048-2
AC(No symmetry value/symmetry value)
550V 600V 2.5 5 5
440V 480V 2.5 7.5 7.5
380V 7.5 14 14
220V 240V 10 25 25
IEC60947-2
Icu
AC
500V 2.5 5 5
440V 2.5 7.5 7.5
415V 5 10 10
380V 7.5 14 14
240V 10 25 25
DC 250V 2.5 5 5
125V 5 10 10
Connection Way Press termianl
Shopping Fitting Alarming Switch(AL) - - o
Auxiliary Switch(AUX) - - o
Voltage Release Mounting(SHT) - - o
Low Voltage Release Mounting(UVT) - - o
Accessory Lead Wire Terminal Platform(LT) - - o
Outer Operate Handle o o o
Terminal Isolation Cover - o o
Automatic Tripping Device Complete electromagenetism type Thermal electromagenetism type
Trip Button - Have

Type ABS 103 ABS 203 ABS 403
Rated Current In(A) 40℃
Reference ambient temperature 40℃
10, 15, 20, 30, 40, 50, 60, 75 100 125, 150, 175, 200, 225 250, 300, 350, 400
Number of Poles 2 3 4 3 3
Max Rated Service Voltage Ui(V) AC 600 600 600
DC 250 250 250
Dimensions and Mounting Details   a 60 90 120 105 140
b 155 165 257
c 56 56 95
ca 82 84 145
bb 132 126 215
aa 0 30 60 30 44
Dimensions and Mounting Details(KA) GB14048-2
AC(No symmetry value/symmetry value)
550V 600V 10 10 22
440V 480V 14 14 35
380V 25 25 42
220V 240V 50 50 50
IEC60947-2
Icu
AC
500V 10 10 22
440V 14 14 35
415V 14 25 35
380V 25 25 42
240V 50 50 50
DC 250V 20 20 30
125V 14 14 20
Connection Way Press termianl
Shopping Fitting Alarming Switch(AL) - o o
Auxiliary Switch(AUX) - o o
Voltage Release Mounting(SHT) - o o
Low Voltage Release Mounting(UVT) - o o
Accessory Lead Wire Terminal Platform(LT) - o o
Outer Operate Handle - o o
Terminal Isolation Cover o - o o
Automatic Tripping Device - - Thermal electromagenetism type
Trip Button - Have


Previous Page: SKM8 Series Moulded Case Circuit Breaker